Standard ASHRAE Equal-Friction Reference Table
Most US residential HVAC supply trunks target 0.08 to 0.10 in. wg per 100 ft equivalent length while keeping branch velocity below 750–900 FPM for quiet airflow.
| Airflow (CFM) | Target Friction (0.08 in.wg) | Target Friction (0.10 in.wg) | Typical Branch Velocity | Equivalent Rect. (8 in height) |
|---|---|---|---|---|
| 100 CFM | 6 in round | 6 in round | ~510 FPM | 4 x 8 in |
| 250 CFM | 8 in round | 8 in round | ~716 FPM | 8 x 8 in |
| 400 CFM | 10 in round | 9 in round | ~905 FPM | 10 x 8 in |
| 800 CFM | 14 in round | 12 in round | ~1,019 FPM | 16 x 8 in |
| 1,200 CFM | 16 in round | 14 in round | ~1,123 FPM | 22 x 8 in |
| 1,600 CFM | 18 in round | 16 in round | ~1,146 FPM | 28 x 8 in |
How Equal-Friction Duct Sizing Works
The equal-friction method keeps pressure drop constant per 100 feet of equivalent duct length across the system (f = 0.109136 x CFM^1.9 / D^5.02 in standard 0.075 lb/ft3 dry air). Once round diameter D is determined, Huebscher's equivalent-diameter formula (De = 1.30 x (a x b)^0.625 / (a + b)^0.25) finds a rectangular trunk duct with identical friction loss for tight joist bays.
Recommended Maximum Air Velocities by Application
Exceeding 900 FPM in bedroom branches or 1,200 FPM in main trunks increases register whistle and static pressure fan draw. Return trunks are often sized slightly larger or at lower velocity (600–800 FPM) near the air handler to control grille intake noise. Continue to our Conduit Bending Calculator or Concrete Yardage Calculator for other MEP trades.