Free Conduit Bending Calculator (Offsets, Saddles & 90-Deg Stubs)

Compute exact bend mark spacing, conduit shrinkage per inch, 3-point and 4-point saddle layouts, and EMT 90-degree stub-up deducts in seconds.

Bend Type
Bend Angle
Distance Between Bend Marks
12.00 in
Multiplier2.00x
Shrink per Inch0.25 in/in
Total Shrinkage1.50 in
Bender Angles30° / 30°

Add total shrinkage to your distance-to-obstacle mark before making the first bend.

Electrician Conduit Offset & Shrinkage Reference Table

Use 30-degree bends as the field default whenever clearance allows because the 2.00x multiplier is easy to verify on the jobsite and keeps wire pulling smooth.

Bend Angle Distance Multiplier Shrinkage per Inch of Offset Typical Field Application
10 deg 5.76x 1/16 in (0.0625 in) Shallow box offsets & minor alignment
22.5 deg 2.61x 3/16 in (0.1875 in) 3-point saddles & moderate clearance
30 deg 2.00x 1/4 in (0.250 in) Standard obstacle offsets (easiest math)
45 deg 1.41x 3/8 in (0.375 in) Tight space offsets & 4-pt saddles
60 deg 1.15x 1/2 in (0.500 in) Steep drops (harder wire pull)

Offset vs. 3-Point vs. 4-Point Saddle Bending

Standard box or structural offsets use two equal opposing angles spaced at Offset x Multiplier. A 3-point saddle clears round pipe obstacles with a center 45-deg bend flanked by two 22.5-deg outer bends (2.5 x height spacing, 3/16 in/in shrink). Rectangular beams or wide trays use a 4-point saddle made of two mirrored offsets around the obstacle width.

Standard 90-Degree Stub-Up Deducts for Hand Benders

Always subtract the bender shoe's take-up (5 in for 1/2" EMT, 6 in for 3/4" EMT, 8 in for 1" EMT, 11 in for 1-1/4" EMT) from your finished vertical stub height before aligning the mark on the bender arrow. Need duct or foundation numbers next? Open our HVAC Ductulator or Concrete Yardage Calculator.

Frequently Asked Questions

What is the distance between marks for a 6-inch offset at 30 degrees?

Multiply the 6-inch offset by 2.00 to place marks 12 inches apart, and compensate for 1.5 inches of shrink (6 x 0.25 in).

What is the take-up deduct for a 90-degree stub on 3/4-inch EMT?

Standard hand bender deducts are 5 inches for 1/2-inch EMT, 6 inches for 3/4-inch EMT, and 8 inches for 1-inch EMT.

Why do electricians add conduit shrinkage before cutting or marking?

Shrinkage shortens overall conduit length as bends pull pipe away from the straight run; you add total shrink to your obstacle measurement when bending toward an obstruction.